(RK01)
319
Single Conductors
K
Suitable accessories can found Chapter X.5
Ⴠ Ⴠ
Special rubber-insulated single core cables
to DIN VDE 0250 part 602
Oil resistant
Test DIN VDE 0473-811-404/
DIN 60811-404
Ⴠ Temperature range
flexing -25°C +80°C
fixed installation -40°C +80°C
Ⴠ Behaviour fire
to DIN VDE 0482-332-1-2
DIN 60332-2-1, IEC 60332-1 (equivalent
DIN VDE 0472 part 804 test method B)
Ⴠ EPR-insulation, compound type 3GI3 to
DIN VDE 0207 part 20
Ⴠ Outer casing: Polychloroprene 5GM3
acc.
Weight
approx. permissible operating voltage
in three and one-phase alternating
current operation U0/U 2,1/3,6 kV, for
direct current operation U0/U 2,7/5,4 kV
Ⴠ Test voltage kV
Ⴠ Minimum bending radius
flexing 10x outer Ø
fixed installation outer Ø
Note
Ⴠ Version available request.
mm²
Part no.
kg km
Cop.
kg km
Cop.
Application
Particularly suitable for protection against short circuits laying and for inherently earth-fault-proof routing rail vehicles and omnibuses. mm
No. Also
suitable for laying dry environments.
Ⴠ AWG sizes are approximate equivalent
values. mm
No.
weight
kg km
Outer Ø
approx.
mm²
Part no.
weight
kg km
Outer Ø
approx.NSGAFÖU 3kVSpecial Rubber-Insulated Cable, VDE approved, short-circuit
up 1000 V
Properties
Cable structure
Technical data
Ⴠ Tinned copper, fine wire conductors, bunch
stranded DIN VDE 0295 cl.
16
62,0
14,4
7,0
1 1,5
38501 1
650,0
480,0
18,0
1 50
38509
14
76,0
24,0
7,5
1 2,5
38502 2/0
900,0
672,0
20,5
1 70
38510
12
95,0
38,0
9,0
1 4
38503 3/0
1200,0
912,0
24,0
1 95
38511
10
140,0
58,0
9,5
1 6
38504 4/0
1450,0
1152,0
26,0
1 120
38513
8
190,0
96,0
11,0
1 10
38505 300 kcmil
1800,0
1440,0
28,0
1 150
38514
6
270,0
154,0
13,0
1 16
38506 350 kcmil
2200,0
1776,0
31,0
1 185
38512
4
410,0
240,0
15,0
1 25
38507 500 kcmil
2650,0
2304,0
34,5
1 240
38515
2
490,0
336,0
16,5
1 35
38508 600 kcmil
3250,0
2880,0
38,0
1 300
38516
Dimensions and specifications may changed without prior notice.5 and
IEC 60228 cl. DIN VDE 0207 part 21
Ⴠ Permissible operating temperature
at conductor +90°C
Ⴠ Colour black Considered being short-circuit safe and
inherently earth-fault-proof are those
operating materials and conducting
assemblies where because suitable
measures and/or means applied, neither a
short circuit nor short ground be
expected under operating conditions which
are accordance with those specified for
the intended application.
Weight
approx.
AWG-No. The actual cross-section mm².cores x
cross-sec.
• Core end sleeve ADI
• Core end sleeve ADU
.
Ⴠ Nominal voltage U0/U 1,8/3 kV
Ⴠ Max. AWG-No.cores x
cross-sec