Poznámky redaktora
weight
kg km
Outer Ø
approx.6
Ⴠ Ⴠ
Bio-oil resistant, abrasion resistant special
high flexible control cable adapted to
DIN VDE 0285-525-1 DIN 50525-1
Resistant to
Bio-fuel (diesel and petrol), highly resistant
to biologically decomposable oils, Oxygene,
Ozone, Hydrolysis and Microbes
Ⴠ Ⴠ
Temperature range
flexing -20°C +80°C
fixed installation -40°C +80°C
Core insulation special polymer with
improved sliding ability Low adhesion
Ⴠ Core identification DIN VDE 0293
black cores with continuous white
numbering
Note
Ⴠ Nominal voltage U0/U 300/500 V
Ⴠ Test voltage 3000 with green-yellow conductor
x without green-yellow conductor (OZ)
Ⴠ GN-YE conductor, cores and above
in the outer layer
Ⴠ Insulation resistance
min.
AWG-No. especially suited for use the machine, tool making and plant industries well as
in the steel industry for difficult and problem areas. The
high flexibility this cable type makes quick and easy install. Further technical details see selection table for drag chain cables, see lead text.cores x
cross-sec. Due to
its high resistance Bio-fuel, Bio-oil and coolant emulsions. For applications which beyond standard solutions (for example for composting appliances high shelf conveyors with
extremely high processing speeds etc. Before installation in
cable trays please read the instructions.
EMC Electromagnetic compatibillity
To optimize the EMC features recommend large round contact the copper braiding both ends. 85% coverage
Ⴠ Radiation resistance
up 100x106 cJ/kg (up 100 Mrad) Wrapping with fleece guarantees good
dismantling
Ⴠ Outer sheath special polymer compound
Ⴠ Sheath colour dark green
Ⴠ with meter marking
Application
HELUKABEL® BIOFLEX-500®-JZ-HF-C extremely robust and high flexible control cable with high abrasion and tear resistant properties.
20
90,0
47,0
7,5
2 0,5
25826 18
188,0
99,0
11,8
5 1
25849
18
235,0
125,0
12,7
7 1
25850
20
104,0
52,0
7,8
3 0,5
25827
20
123,0
55,0
8,2
4 0,5
25828 18
340,0
178,0
14,6
10 1
25851
18
358,0
186,0
15,5
12 1
25852
20
131,0
65,0
9,9
5 0,5
25829
20
172,0
84,0
10,0
7 0,5
25830 18
415,0
250,0
16,7
14 1
25853
18
500,0
280,0
18,0
18 1
25854
20
230,0
115,0
11,3
10 0,5
25831
20
250,0
117,0
12,5
12 0,5
25832 18
678,0
378,0
21,0
25 1
25855
20
280,0
148,0
13,2
14 0,5
25833 16
141,0
79,0
10,5
2 1,5
25856
20
321,0
157,0
14,5
18 0,5
25834 16
164,0
94,0
10,8
3 1,5
25857
20
445,0
227,0
16,8
25 0,5
25835 16
220,0
113,0
11,5
4 1,5
25858
19
106,0
53,0
8,3
2 0,75
25836 16
233,0
129,0
12,5
5 1,5
25859
16
323,0
170,0
13,2
7 1,5
25860
19
120,0
62,0
8,5
3 0,75
25837
19
150,0
77,0
9,5
4 0,75
25838 16
369,0
226,0
14,4
8 1,5
25861
16
461,0
258,0
14,9
10 1,5
25862
19
158,0
86,0
10,8
5 0,75
25839
19
205,0
107,0
11,5
7 0,75
25840 16
481,0
280,0
16,2
12 1,5
25863
16
561,0
340,0
18,1
14 1,5
25864
19
290,0
148,0
13,1
10 0,75
25841
19
304,0
156,0
14,0
12 0,75
25842 16
672,0
395,0
20,3
18 1,5
25865
16
780,0
461,0
21,7
21 1,5
25866
19
380,0
214,0
15,3
14 0,75
25843
19
418,0
235,0
17,3
18 0,75
25844 16
927,0
533,0
23,1
25 1,5
25867
19
578,0
313,0
18,7
25 0,75
25845 14
185,0
96,0
11,8
2 2,5
25868
18
116,0
60,0
10,0
2 1
25846 14
278,0
150,0
13,0
3 2,5
25869
14
370,0
174,0
14,0
4 2,5
25870
18
135,0
70,0
10,2
3 1
25847
18
178,0
86,0
11,0
4 1
25848 14
412,0
200,0
15,1
5 2,5
25871
Continuation Ⴇ
182
Cables for Drag Chains Bio-Oil and microbial resistant Cables for Drag Chains
.
Weight
approx. AWG-No.6 and IEC 60228 cl. Suitable for outdoor lying. The actual cross-section mm².
= The product conformed with the Low-Voltage Directive 2006/95/EC.
weight
kg km
Outer Ø
approx.cores x
cross-sec.
Ⴠ Cores stranded layers with optimal selected
lay-length
Ⴠ Minimum bending radius
flexing 15x cable Ø
fixed installation cable Ø
Ⴠ unsreened analogue type:
BIOFLEX-500®-JZ-HF, confer page 181
Ⴠ Wrapping with fleece
Ⴠ Special inner sheath
Ⴠ Coupling resistance
max.
mm²
Part no.) recommend for our especially developed enquiry sheet for energy guiding systems. MOhm AWG sizes are approximate equivalent
values.
kg km
Cop. mm
No. These screened cables are particularly suitable for the
interference-free transmission instrumentation and control engineering applications (electromagnetic compatibillity). 250 Ohm/km Copper braided screening
approx. For the critical applications
we advise for consultation.6,
BS 6360 cl.
kg km
Cop.BIOFLEX-500®-JZ-HF-C Biofuel-resistant, abrasion-resistant, recyclable,
environmentally friendly, drag-chain cable, bio-oil resistant 1), meter marking
Properties
Cable structure
Technical data
Ⴠ Bare copper, extra fine wire conductors,
bunch stranded DIN VDE 0295 cl. Suitable combination with cable trays dry, moist and wet rooms and outdoor installation. mm
No.
mm²
Part no.
Weight
approx