6/1kV 4000V, 50Hz
General Properties
Minimum bending Radius
Distribution boxes
Operating temperature Zero halogen non corrosive gases Flame retardant Fire resistant (no flame propagation) Minimum smoke emission
pyrofil® (N)HXH FE180/E90 Keram 0708/e
during and permanent installation 15* (single core cable) 12* (multicore cable) outer diameter) permanent installation *50% reduction installation 30°C and with template permanent installation -45°C +90°C during installation -5°C +50°C
IEC 60754-2, 50267-2-2, VDE 0482-267-2-2 IEC 60332-1-2, 60332-1-2, VDE 0482-332-1-2 IEC 60332-3-22/-24 Cat. A/C IEC 61034-1/-2, 61034-1/-2 (EN 50268-1/-2), VDE 0482-1034-1/-2 (VDE 0482-268-1/-2) Circuit integrity (FE180) IEC 60331-11/-21 (180 minutes), VDE 0472 part 814, 6387 CWZ System Circuit integrity E90 DIN 4102 part System Circuit integrity under effect water VdS 3423 [single core cable ≥16mm2]
P-66
Informations
Accessories
Technical changes reserved. A/C, 50266-2-2/-4 Cat. These cables correspond the demands system circuit integrity E90 accordance with DIN 4102-12. A/C, VDE 0482-266-2-2/-4 Cat.” “YEAR” “METRE MARKING”
Electrical Properties
Firestop systems
Nominal voltage Test voltage
0.
Construction
Support systems
Conductor Insulation Filler Outer sheath Core colours Sheath colour Imprint
Fixing devices
Bare copper, solid stranded IEC 60228, 60228, (VDE 0295) Double insulation, cross-linked, high-performance Keram special compound according VDE 0266 “HXI1” Flame retardant, halogenfree, thermoplastic compound Flame retardant, Polyolefin compound according CENELEC 604 and VDE 0276-604 “HM4” According CENELEC 308 and VDE 0293 orange DAETWYLER PYROFIL KERAM (N)HXH FE180 E90 1kV MM2” VDE REG. System circuit integrity guaranteed operating voltage 400V.
.pyrofil® Keram (N)HXH FE180 E90
Safety low voltage cable 0. The cable should only laid directly earth water protective conduit used. For outdoor applications, protection must provided against exposure direct sunlight. 7780 “VDS“ “ORDER NO. Suitable for indoor applications.6/1kV Halogen-free, with improved fire characteristics With reference VDE 0266 and CENELEC 604 Circuit integrity (FE180) accordance with VDE 0472-814, IEC 60331 System Circuit integrity E90 accordance with DIN 4102-12
Filler Flame retardant, zero halogen Fire barrier High-peformance Keram compound
Preventive fire protection
Sheath FRNC/LS0H
Insulation Crosslinked polymer zero halogen
Conductor Solid/ stranded
Product information
Application
Safety cables