For outdoor applications, protection must provided against exposure direct sunlight.6/1kV 4000V, 50Hz
Firestop systems
Fixing devices
Electrical Properties
Nominal voltage Test voltage
Distribution boxes
General Properties
Minimum bending Radius
Operating temperature Zero halogen non corrosive gases Flame retardant Fire resistant (no flame propagation) Minimum smoke emission Circuit integrity (FE180) System Circuit integrity E30-E60*
during and permanent installation (single core cable) (multicore cable) outer diameter) permanent installation -45°C +90°C during installation -5°C +50°C IEC 60754-2, 50267-2-2, VDE 0482-267-2-2 IEC 60332-1-2, 60332-1-2, VDE 0482-332-1-2 IEC 60332-3-22/-24 Cat.
Technical changes reserved. These cables correspond the demands circuit integrity E30-E60* accordance with DIN 4102-12. NR. 7800 “ORDER NO. The cable should only laid directly earth water protective conduit used. A/C, 50266-2-2/-4 Cat.
P-62
. A/C, VDE 0482-266-2-2/-4 Cat.
Construction
Support systems
Conductor Insulation Filler Inner sheath Armouring [rodent-protection] Outer sheath Core colours Sheath colour Imprint
Bare copper, solid stranded IEC 60228, 60228, (VDE 0295) Double insulation, cross-linked, high-performance Keram special compound according VDE 0266 “HXI1” Flame retardant, halogenfree, thermoplastic compound Flame retardant, Polyolefin compound according CENELEC 604 and VDE 0276-604 “HM4” Galvanised steel tape Flame retardant, Polyolefin compound according CENELEC 604 and VDE 0276-604 “HM4” According CENELEC 308 and VDE 0293 orange DAETWYLER PYROFIL KERAM (N)HXH FE180 E30-E60 1kV MM2” VDE REG. Circuit integrity guaranteed operating voltage 400V.pyrofil® Keram (N)HXH FE180 E30-E60
Safety low voltage cable 0.6/1kV armoured with rodent-protection Halogen-free, with improved fire characteristics With reference VDE 0266 and CENELEC 604 Circuit integrity (FE180) accordance with VDE 0472-814, IEC 60331 System Circuit integrity E30-E60* accordance with DIN 4102-12
Filler Flame retardant zero halogen Fire barrier High performance Keram special compound
Preventive fire protection
Sheath FRNC/LS0H
Armouring Galvanised steel tape
Inner sheath Polyolefin flame retardant, low smoke, zero halogen
Insulation Crosslinked polymer zero halogen
Conductor Solid/stranded
Product information
Application
Safety cables
Safety cables are used all situations that require special protection against fire and flame damage for people and equipment and where high degree safety conditions must fulfilled. Suitable for indoor applications. Permitted operating temperature conductor +90˚C. A/C IEC 61034-1/-2, 61034-1/-2 (EN 50268-1/-2), VDE 0482-1034-1/-2 (VDE 0482-268-1/-2) IEC 60331-11/-21 (180 minutes), VDE 0472 part 814, 6387 CWZ DIN 4102 part 12
Accessories
pyrofil® (N)HXH FE180/E30-E60 Keram 0708/e
Informations
* System Circuit integrity dependent installation method.” “YEAR” “METRE MARKING” 0