These cables correspond the demands system circuit integrity E30-E60* accordance with DIN 4102-12. Conductor Insulation Bare copper, solid stranded IEC 60228, 60228, (VDE 0295) Double insulation, cross-linked, high-performance Keram special compound according VDE 0266 “HXI1” Flame retardant, halogenfree, thermoplastic compound Flame retardant, Polyolefin compound according CENELEC 604 and VDE 0276-604 “HM4” According CENELEC 308 and VDE 0293 orange DAETWYLER PYROFIL KERAM (N)HXH FE180 E30-E60 1kV MM2” VDE REG. The cable should only laid directly earth water protective conduit used. Suitable for indoor applications. A/C, VDE 0482-266-2-2/-4 Cat. Permitted operating temperature conductor +90˚C.pyrofil® Keram (N)HXH FE180 E30-E60
Safety low voltage cable 0. NR. A/C IEC 61034-1/-2, 61034-1/-2 (EN 50268-1/-2), VDE 0482-1034-1/-2 (VDE 0482-268-1/-2) IEC 60331-11/-21 (180 minutes), VDE 0472 part 814, 6387 CWZ DIN 4102 part 12, NBN 713.” “YEAR” “METRE MARKING”
Construction
Support systems
Filler Outer sheath Core colours Sheath colour Imprint
Fixing devices
Electrical Properties
Firestop systems
Rated voltage Test voltage
0. System circuit integrity guaranteed operating voltage 400V.
.6/1kV 4000V, 50Hz
General Properties
Minimum bending Radius
Distribution boxes
Operating temperature Zero halogen non corrosive gases Flame retardant Fire resistant (no flame propagation) Minimum smoke emission Circuit integrity (FE180) System Circuit integrity E30-E60*
during and permanent installation 15* (single core cable) 12* (multicore cable) outer diameter) permanent installation *50% reduction installation 30°C and with template permanent installation -45°C +90°C during installation -5°C +50°C IEC 60754-2, 50267-2-2, VDE 0482-267-2-2 IEC 60332-1-2, 60332-1-2, VDE 0482-332-1-2 IEC 60332-3-22/-24 Cat. For outdoor applications, protection must provided against exposure direct sunlight.6/1kV Halogen-free, with improved fire characteristics With reference VDE 0266 and CENELEC 604 Circuit integrity (FE180) accordance with VDE 0472-814, IEC 60331 System Circuit integrity E30-E60* accordance with DIN 4102-12
Filler Flame retardant, zero halogen Fire barrier High-peformance Keram compound
Preventive fire protection
Sheath FRNC/LS0H
Insulation Crosslinked polymer zero halogen
Conductor Solid/ stranded
Product information
Application
Safety cables
Safety cables are used all situations that require special protection against fire and flame damage for people and equipment and where high degree safety conditions must fulfilled. 7780 “ORDER NO. A/C, 50266-2-2/-4 Cat.
P-56
Technical changes reserved.020 (Rf1)
Accessories
pyrofil® (N)HXH FE180/E30-E60 Keram 0708/e
Informations
* System Circuit integrity dependent installation method