50266-2-4 Cat.1. “HIC” Flame retardant, halogenfree, thermoplastic compound Flame retardant, Polyolefin compound according CENELEC 604 part sec.2
Accessories
Fire resistant (no flame propagation) Minimum smoke emission
pyrofil® Keram FE180-CL 0708/e
Informations
Circuit integrity (FE180)
P-52
Technical changes reserved. Permitted operating temperature conductor +90˚C.
. “HMT1” Galvanised steel tape Flame retardant, Polyolefin compound according CENELEC 604 part sec.” “YEAR” “METRE MARKING”
Support systems
Firestop systems
Electrical Properties
Nominal voltage Test voltage
0. “HMT1” According CENELEC 308 orange DAETWYLER PYROFIL KERAM FE180-CL MM2” “ORDER NO.This product has been developed especially for the Swiss market
pyrofil® Keram FE180-CL
Safety low voltage cable 0.4.4.6/1kV 3500V, 50Hz
General Properties
Minimum bending Radius
Distribution boxes
Operating temperature Zero halogen non corrosive gases Flame retardant
during and permanent installation (single core cable) (multicore cable) outer diameter) permanent installation -45°C +90°C during installation -5°C +50°C IEC 60754-2, 50267-2-2, VDE 0482-267--2-2, SEV TP20B/3C 3. Suitable for indoor applications.4 IEC 60332-1-2, 60332-1-2, VDE 0482-332-1-2, SEV TP20B/3C 3.
Construction
Conductor Insulation Filler Inner sheath Armouring/[rodent-protection] Outer sheath Core colours Sheath colour Imprint
Fixing devices
Bare copper, solid stranded IEC 60228, 60228 Double insulation, cross-linked, high-performance Keram special compound according CENELEC 604 part sec.4.H Circuit integrity (FE180) accordance IEC 60331
Inner sheath Polyolefin flame retardant, low smoke, zero halogen Filler Flame retardant, zero halogen Fire barrier High-peformance Keram compound
Preventive fire protection
Sheath FRNC/LS0H
Armouring Galvanised steel tape
Insulation Crosslinked polymer zero halogen
Conductor Solid/stranded
Product information
Application
Safety cables
Safety cables are used all situations that require special protection against fire and flame damage for people and equipment and where high degree safety conditions must fulfilled. For outdoor applications, protection must provided against exposure direct sunlight.6/1kV armoured with rodent-protection Halogen-free, with improved fire characteristics with reference SEV 20B/3C and CENELEC 604 part 5.1. VDE 0482-266-2-4 Cat.3 IEC 60331-11/-21 (180 minutes), VDE 0472 part 814, SEV TP20B/3C 3. The cable should only laid directly earth water protective conduit used.3 IEC 61034-1/-2, 61034-1/-2 (EN 50268-1/-2), VDE 0482-1034-1/-2 (VDE 0482-268-1/-2), SEV TP20B/3C 3.4. SEV TP20B/3C 3.1 IEC 60332-3-24 Cat.4