4.4.4. SEV TP20B/3C 3.4.4.
.This product has been developed especially for the Swiss market
pyrofil® Keram FE180 flex
Control cable flex 300/500V Halogen-free, with improved fire characteristics with reference SEV 20B/3C and CENELEC 604 part 5. VDE 0482-266-2-4 Cat.1. The cable should only laid directly earth water protective conduit used. For outdoor applications, protection must provided against exposure direct sunlight. “HMT1” According CENELEC 308 orange request
Fixing devices
Support systems
Electrical Properties
Nominal voltage Test voltage
300/500V 2000V, 50Hz
Firestop systems
General Properties
Minimum bending Radius Operating temperature Zero halogen non corrosive gases Flame retardant Fire resistant (no flame propagation) Minimum smoke emission
permanent installation during installation permanent installation during installation
4 outer diameter) 6xD -45°C +90°C -5°C +50°C
Circuit integrity (FE180)
IEC 60754-2, 50267-2-2, VDE 0482-267--2-2, SEV TP20B/3C 3.3 IEC 60331-11/-21 (180 minutes), VDE 0472 part 814, SEV TP20B/3C 3.
Construction
Conductor Insulation Filler Outer sheath Core colours Sheath colour Imprint
Bare copper, flexible IEC 60228 class 60228 Double insulation, cross-linked, high-performance Keram special compound according CENELEC 604 part sec. Permitted operating temperature conductor +90˚C. 50266-2-4 Cat. “HIC” Flame retardant, halogenfree, thermoplastic compound Flame retardant, Polyolefin compound according CENELEC 604 part sec.1 IEC 60332-3-24 Cat. Suitable for indoor applications.1.4 IEC 60332-1-2, 60332-1-2, VDE 0482-332-1-2, SEV TP20B/3C 3.H Circuit integrity (FE180) accordance IEC 60331
Filler Flame retardant, zero halogen Fire barrier High performance Keram special compound
Preventive fire protection
Sheath FRNC/LS0H
Insulation Crosslinked polymer zero halogen
Conductor flexible
Product information
Application
Safety cables
Safety cables are used all situations that require special protection against fire and flame damage for people and equipment and where high degree safety conditions must fulfilled.3 IEC 61034-1/-2, 61034-1/-2 (EN 50268-1/-2), VDE 0482-1034-1/-2 (VDE 0482-268-1/-2), SEV TP20B/3C 3.2
Accessories
Distribution boxes
P-50
pyrofil® Keram FE180 flex 0708/e
Informations
Technical changes reserved