4 IEC 60332-1-2, 60332-1-2, VDE 0482-332-1-2, SEV TP20B/3C 3. “HMT1” According CENELEC 308 orange DAETWYLER PYROFIL KERAM FE180 MM2” “ORDER NO. Suitable for indoor applications.3 IEC 60331-11/-21 (180 minutes), VDE 0472 part 814, SEV TP20B/3C 3.1.” “YEAR” “METRE MARKING”
Fixing devices
Electrical Properties
Nominal voltage Test voltage
0.1.6/1kV Halogen-free, with improved fire characteristics with reference SEV 20B/3C and CENELEC 604 part 5.4. SEV TP20B/3C 3.4.This product has been developed especially for the Swiss market
pyrofil® Keram FE180
Safety low voltage cable 0.2
Accessories
Technical changes reserved.H Circuit integrity (FE180) accordance IEC 60331
Filler Flame retardant, zero halogen Fire barrier High-peformance Keram compound
Preventive fire protection
Sheath FRNC/LS0H
Insulation Crosslinked polymer zero halogen
Conductor Solid/stranded
Product information
Application
Safety cables
Safety cables are used all situations that require special protection against fire and flame damage for people and equipment and where high degree safety conditions must fulfilled.
Construction
Conductor Insulation
Support systems
Filler Outer sheath Core colours Sheath colour Imprint
Bare copper, solid stranded IEC 60228, 60228, (VDE 0295) Double insulation, cross-linked, high-performance Keram special compound according CENELEC 604 part sec.6/1kV 3500V, 50Hz
Firestop systems
General Properties
Minimum bending Radius
Distribution boxes
Operating temperature
during and permanent installation 15* (single core cable) 12* (multicore cable) outer diameter) permanent installation *50% reduction installation 30°C and with template permanent installation -45°C +90°C during installation -5°C +50°C
Zero halogen non corrosive gases Flame retardant
Fire resistant (no flame propagation) Minimum smoke emission
Informations
P-46
pyrofil® Keram FE180 0708/e
Circuit integrity (FE180)
IEC 60754-2, 50267-2-2, VDE 0482-267--2-2, SEV TP20B/3C 3. For outdoor applications, protection must provided against exposure direct sunlight.4. Permitted operating temperature conductor +90˚C. VDE 0482-266-2-4 Cat.3 IEC 61034-1/-2, 61034-1/-2 (EN 50268-1/-2), VDE 0482-1034-1/-2 (VDE 0482-268-1/-2), SEV TP20B/3C 3.
. “HIC” Flame retardant, halogenfree, thermoplastic compound Flame retardant, Polyolefin compound according CENELEC 604 part sec. The cable should only laid directly earth water protective conduit used. 50266-2-4 Cat.4.1 IEC 60332-3-24 Cat.4