Information and Communication technology, Safety cable systems, Building automation, Elevator cable systems, Cable harnessing, logistics and support
Strana 362 z 528
Vámi hledaný text obsahuje tato stránku dokumentu který není autorem určen k veřejnému šíření.
Poznámky redaktora
A/C, 50266-2-2/-4 Cat.
. Permitted operating temperature conductor of+90˚C.Armoured pyrofil® Standard Fire safety Cable
Fire alarm cable with steel wire braiding 300/500V Halogen-free, with improved fire characteristics with reference 7629-1
Inner sheath Polyolefin compound
Preventive fire protection
Inner covering Glassfibre tape
Insulation Fire resistant Special compound, according 7655, low smoke, zero halogen
Sheath FRNC/LS0H
Armouring galvanised steel wire braid
Shielding Alu-laminated tape
Drain wire Tinned copper
Conductor Solid/ stranded
Product information
Application
Safety cables
Armoured cable for fire alarm systems and emergency lighting for permament installation buildings. 7655, “EI5” cores earth: brown, blue cores earth: brown, black, grey cores earth: brown, black, grey, blue Glasfibre tape Al-laminated tape and tinned copper drain wire acc. A/C IEC 61034-1/-2, 61034-1/-2 (EN 50268-1/-2), VDE 0482-1034-1/-2 (VDE 0482-268-1/-2) IEC 60331-11/-21 (180 minutes), VDE 0472 part 814, 6387 CWZ, 50200 (PH120), VDE 0482-200
Accessories
Distribution boxes
P-44
pyrofil® Standard Fire Safety Cable 0708/e
Informations
Technical changes reserved.
Construction
Conductor Insulation Core colours Inner covering Shielding
Fixing devices
Inner sheath Armouring Outer Sheath Sheath colour Imprint
Bare copper, solid stranded IEC 60228 class 60228 (BS 6360) Double insulation, cross-linked special compound acc. A/C, VDE 0482-266-2-2/-4 Cat. IEC 60228 class 1or 60228 and (BS 6360) Polyolefin compound GSWB, galvanised steel wire braid Polyolefin compound acc. 7655 “LTS3” red (white black request) request
Support systems
Electrical Properties
Firestop systems
Nominal voltage Test voltage
300/500V 2000V, 50Hz
General Properties
Minimum bending radius Operating Temperature Zero halogen non corrosive gases Flame retardant Fire resistant (no flame propagation) Minimum smoke emission Circuit integrity (FE180)
during and permanent installation outer diameter) permanent installation -15°C +90°C during installation -5°C +50°C IEC 60754-1/-2, 50267-2-1/-2-2, VDE 0482-267-2-1/-2-2 IEC 60332-1-2, 60332-1-2, VDE 0482-332-1-2 IEC 60332-3-22/-24 Cat