Open the circuit-breaker.
The signals are given correctly.
The circuit-breaker closes correctly. The
signals are correct.
Carry out some racking-in and out operations. The signals
are correct.
The springs are loaded correctly.
The signals are correct.
Supply the spring loading geared motor the
corresponding rated voltage.
Carry out the operating tests.
The circuit-breaker opens correctly.
The circuit-breaker closes correctly.
Model 2234 Apparatus Scale
L 2778
Doc-Na 1SDH000460R0002
Page No.
CAUTION
When there undervoltage release, the
circuit-breaker can only closed after the
release has been electrically energized. Interlocking
devices between circuit-breakers side by
side and one top another (if any)
10 For withdrawable circuit-breakers: racking
-in/out device
P re
Carry out some opening and closing operations
(see the chapter 7. Carry out some circuit-breaker closing
and opening operations.
Both anual and electrical closing are
prevented.
C arry som sin and ning
operations.
P itiv ck
The spring loading lever moves correctly.
Close the circuit-breaker. The signal changes
over. Supply the undervoltage release the
corresponding rated voltage (if any).
The circuit-breaker opens.
Supply the shunt opening release the
corresponding rated voltage.1 eneral s
- Check tightness the power connections the circuit-breaker terminals
- Carry out all the preparatory operations the release
- Make sure that the value the auxiliary circuit power supply voltage between and 110% the rated voltage the electrical applications
- Make sure that there adequate air circulation the place installation avoid overheating
- Also carry out the checks specified the following table.2).
ite d
1 Manual operating mechanism
2 Geared motor (if any)
3 Undervoltage release
(if any)
4 Shunt opening release (if any)
5 Shunt closing release (if any)
6 Circuit-breaker lock the open position
(with key padlocks)
7 Auxiliary contacts the circuit-breaker
8 Auxiliary contacts for signalling circuit-
breaker connected, test isolated and
disconnected
9 Lock vice circ it-b rs
connected and disconnected.
Open the circuit-breaker, turn the key and
remove from its seat.
Note.
Disconnect voltage the release.
The geared otor stops with the springs
loaded.
The locks function correctly. The signals
are correct.
S upply the undervoltage release the
corresponding rated voltage and carry out the
circuit-breaker closing operation.
Insertthe auxiliary contacts suitable signalling
circuits.Putting into service
6.
15/158
.
Supply the shunt closing release its rated
voltage.
The signals due the relative operations are
given correctly.
S upply the undervoltage release the
corresponding rated voltage and carry out the
circuit-breaker closing operation.
Insertthe auxiliary contacts suitable signalling
circuits.
Racking-in operation: the circuit-breaker racks
in correctly. Then put the circuit-breaker the
connected, test isolated and disconnected
position.
The geared motor reloads the springs after
each closing operation. The first turns the crank handle
do not meet with particular resistance. Attempt circuit-breaker
closing operation