The circuit-breaker opens correctly. Supply the undervoltage release the corresponding rated voltage (if any). Supply the shunt opening release the corresponding rated voltage. The circuit-breaker closes correctly. Open the circuit-breaker, turn the key and remove from its seat. CAUTION When there undervoltage release, the circuit-breaker can only closed after the release has been electrically energized. The circuit-breaker closes correctly. Racking-in operation: the circuit-breaker racks in correctly. Carry out some circuit-breaker closing and opening operations. The locks function correctly. The geared motor reloads the springs after each closing operation. Carry out the operating tests. Close the circuit-breaker. Item inspected 1 Manual operating mechanism 2 Geared motor (if any) 3 Undervoltage release (if any) 4 Shunt opening release (if any) 5 Shunt closing release (if any) 6 Circuit-breaker lock the open position (with key padlocks) 7 Auxiliary contacts the circuit-breaker 8 Auxiliary contacts for signalling circuit- breaker connected, test isolated and disconnected 9 vice irc it-b rs connected and disconnected.Putting into service 6. S upply the undervoltage release the corresponding rated voltage and carry out the circuit-breaker closing operation. The signals due the relative operations are given correctly. The signals are given correctly. Disconnect voltage the release. The geared motor stops with the springs loaded. Positive check The spring loading lever moves correctly. The signals are correct. Supply the spring loading geared motor the corresponding rated voltage. The signals are correct. Open the circuit-breaker. The signal changes over. Insert the auxiliary contacts suitable signalling circuits. Then put the circuit-breaker the connected, test isolated and disconnected position. Interlocking devices between circuit-breakers side by side and one top another (if any) 10 For withdrawable circuit-breakers: racking -in/out device Procedure Carry out some opening and closing operations (see the chapter 7. The first turns the crank handle do not meet with particular resistance. Both anual and electrical closing are prevented. C arry som sin and g operations. The signals are correct.2). Note. The springs are loaded correctly. The signals are correct. 14/1 08 . Attempt circuit-breaker closing operation. S upply the undervoltage release the corresponding rated voltage and carry out the circuit-breaker closing operation. The circuit-breaker opens. Model L3447 A pparatus Emax DC S cale D oc-N 1SDH000635R0002 Page No. Insert the auxiliary contacts suitable signalling circuits. Carry out some racking-in and out operations. Supply the shunt closing release its rated voltage.1 eneral res - Check tightness the power connections the circuit-breaker terminals - Carry out all the preparatory operations the release - Make sure that the value the auxiliary circuit power supply voltage between and 110% the rated voltage the electrical applications - Make sure that there adequate air circulation the place installation avoid overheating - Also carry out the checks specified the following table