Poznámky redaktora
Countdown programmed starting time (normally then begins.. Its usual designation «400 690 motor».. contactor delta con
tactor, the use tim including dwelling tim (or transition time) e.
An electrical interlock between star and delta mandatory such through auxiliary contacts.
(Switching frequency/hour, according acceleration time and load factor).. mainly the decreasing rotation speed acceptable during the starting phase.
Transient current generated when switching from star delta connec
tion.
5
1SBC101001C0202
.
2nd stage «Star» «Delta» switching When the programmed starting time over, the KM2 «star» contactor opens.
Furthermore, open transition, the current interruption may reach ms: shall checked that this duration compatible with the ap
plication i. TE5S not recommended.. contactor star contactor with ..
This starting mode therefore ideal for machines having low starting
torque such as:
- pumps,
- centrifugal compressors,
- wood-working machines, etc.
In order prevent high current peak, least nominal speed
must reached before switching from star delta. This system can used all the squirrel cage motors,
which are normally used delta connection.
Example:
- Switching frequency sta rts/h r
- Acceleration time "ta" (use curve)
- Maximum load factor %
This corresponds 4-minute operating cycle (15 starts/hr) with seconds acceleration,
2 minutes operation and minutes rest.
Utilization
During the initial starting phase («star» connection), the resistive torque
of the driven load must remain, irrespective speed, less than the «star»
motor torque until «star-delta» switching occurs.
The motor must constructed with terminal windings.
Maximum duty per the chart side.g. contactor types are used delta and star contactors ..General Inform ation
Star-Delta Starting
of Three-Phase Asynchonous Motors
General
Star-delta starting the most common method reduce the starting current motor. The KM1 «line» contactor then
closes and the motor starts.e.
Note:
When . This prevents short circuit between «star» and «delta».
3rd stage «Delta» connection transition time (or dwelling time) fixed between opening the «star» contactor and closing of
the «delta» contactor the use TE5S timer.
Respect the following conditions enables utilization the starter without excessive
overheating the connections nuisance tripping the thermal O/L relay. much higher than the resistive torque order reach
sufficient high speed when the motor connected star.
Precautions
M otor nominal voltage delta connection must equal that the mains.
Exam ple: motor for 400 star-delta starting must designed for 400 «delta» connection.
Sequence
Starting three-stage process:
1st stage «Star» connection Press the «On» button the control circuit close the KM2 «star» contactor.
Star-Delta Starting
Technical Data
When starting:
- inrush current reduced third direct starting current,
- motor torque reduced third even less direct starting torque.
In this type starting, recommended choose motors having high starting torque i. timer set for the starting duration star
connection enough.e