- application safe xiliary pow supply (as diagram 2), fuses
must selected according the electrical rating the otor operators or
control coils (see technical catalogue relevant irc breaker range).
F line -to -lin voltages low er, odular irc breakers can be
selected follow s:
- application safe auxiliary power supply (as diagrams and 4):
Q61/1 2-pole odular circu breaker In= (S252 C1)
Q61/2: 4-pole odular circu breaker In= (S254 C1)
- application safe auxiliary pow supply (as diagram 2), devices
must selected according the short-circuit current calculated the ain
breakers:
7.
How select Q61/1 and Q61/2
Fuses odular irc breakers used, depending specific installation
requirements.These devices are used protect:
- the ATS010 circuits
- the circu breaker otor operators control coils, they are powered norm al
and emergency lines (see circu diagram ithout safe auxiliary pow supply").
ABB SACE SACE ATS010 RH0202002 L2467.5 Q61/1
Q61/2
2-pole modular circuit breaker In=6A(C), series S240 S242 )
4-pole modular circuit breaker In=6A(C), series S240 S244 )
<= Q61/1
Q61/2
2-pole modular circuit breaker In=6A(C), series S250 S252 )
4-pole modular circuit breaker In=6A(C), series S250 S254 )
<= Q61/1
Q61/2
2-pole modular circuit breaker In=6A(C), series S270 S272 )
4-pole modular circuit breaker In=6A(C), series S270 S274 )
<= Q61/1
Q61/2
2-pole modular circuit breaker In=6A(C), series S500 S502 )
4-pole modular circuit breaker In=6A(C), series S500 S504 )
> (**) Q61/1 and Q61/2 fuses gG6 (total quantity: 6)
(* allow application, gG6 fuses can also used short
c irc currents.
Fuses are selected follo s:
- plication safe xiliary pow supply (as diagram 3
and 4), fuses should used.1 Protection devices Q61/1, Q61/2
short circuit current
<= 7.5