Lightning protection guide by OBO

| Kategorie: Katalog  |

Last revision 2020

Vydal: OBO BETTERMANN s. r. o. Autor: OBO BETTERMANN

Strana 197 z 288

Jak získat tento dokument?






Poznámky redaktora
5 wiring must selected. Solution options: • Installation second SPD near to the resource protected • Use wiring • Local equipotential bonding (e.TBS Blitzschutz-Leitfaden 2018 / en / 2020/01/10 14:42:40 14:42:40 (LLExport_02613) / 2020/01/10 14:42:54 14:42:54 V wiring surge arrestor according IEC 60634-5-53 lightning current Utotal = surge voltage protection device) The connection cable the protection device cru- cial for achieving optimum protection level. A pulse current 8/20 gener- ates voltage drop per metre of cable. with the metal housing the switchgear cabinet) TBS Blitzschutz-Leitfaden 2018 / en / 2020/01/10 14:42:40 14:42:40 (LLExport_02613) / 2020/01/10 14:42:54 14:42:54 197 Chapter The internal lightning protection system .g. In accordance with IEC installation directives, the length the branch cable the arrestor and the length the line from the protection device the equipotential bonding should, total, less than 0.5 the cables are longer than 0