Lightning protection guide by OBO

| Kategorie: Katalog  |

Last revision 2020

Vydal: OBO BETTERMANN s. r. o. Autor: OBO BETTERMANN

Strana 168 z 288

Jak získat tento dokument?






Poznámky redaktora
These voltages need reduced via potential control insulation. This is particularly required areas with groups people. 100 kV (1.1 Step voltage The step voltage the voltage between person’s feet placed apart.2 Protection against dangerous touch voltage The isCon® conductor Pro+ can used as protection against dangerous touch voltage. The contact voltage the voltage between component (e.6. with pulse voltage min. U B1 U B2 U E U S FE FE SE + 1m UE : Earthing voltage UB1 : Touch voltage without potential control (on founda- tion earth electrode) UB2 : Touch voltage with potential control (foundation earth electrode and control earther) Us : Step voltage (without control earther) φ: Earth surface potential FE: Foundation earth electrode SE: Control earth electrode (ring earth electrode) Electrical potential the earth surface and voltages current passes through the foundation earth electrode (FE) and control earther (SE) TBS Blitzschutz-Leitfaden 2018 / en / 2020/01/10 14:42:40 14:42:40 (LLExport_02613) / 2020/01/10 14:42:54 14:42:54 168 Chapter The external lightning protection system . Here the current flows from the hand the foot through the body. the conductor) and earth potential. Here the current flows between the person's feet through their body.2/50 μs) rain and fulfils the requirements for touch protection according IEC/EN 62305-3.6. 2.2.g. The isCon® conductor Pro+ was tested a length max. Both types voltage can harm- ful the body