Lightning protection guide by OBO

| Kategorie: Katalog  |

Last revision 2020

Vydal: OBO BETTERMANN s. r. o. Autor: OBO BETTERMANN

Strana 168 z 288

Jak získat tento dokument?






Poznámky redaktora
6. U B1 U B2 U E U S FE FE SE + 1m UE : Earthing voltage UB1 : Touch voltage without potential control (on founda- tion earth electrode) UB2 : Touch voltage with potential control (foundation earth electrode and control earther) Us : Step voltage (without control earther) φ: Earth surface potential FE: Foundation earth electrode SE: Control earth electrode (ring earth electrode) Electrical potential the earth surface and voltages current passes through the foundation earth electrode (FE) and control earther (SE) TBS Blitzschutz-Leitfaden 2018 / en / 2020/01/10 14:42:40 14:42:40 (LLExport_02613) / 2020/01/10 14:42:54 14:42:54 168 Chapter The external lightning protection system . with pulse voltage min. Here the current flows from the hand the foot through the body. Both types voltage can harm- ful the body. 2.g.2 Protection against dangerous touch voltage The isCon® conductor Pro+ can used as protection against dangerous touch voltage.2. These voltages need reduced via potential control insulation. The contact voltage the voltage between component (e. The isCon® conductor Pro+ was tested a length max.6. 100 kV (1. This is particularly required areas with groups people. the conductor) and earth potential. Here the current flows between the person's feet through their body.2/50 μs) rain and fulfils the requirements for touch protection according IEC/EN 62305-3.1 Step voltage The step voltage the voltage between person’s feet placed apart