Lightning protection guide by OBO

| Kategorie: Katalog  |

Last revision 2020

Vydal: OBO BETTERMANN s. r. o. Autor: OBO BETTERMANN

Strana 108 z 288

Jak získat tento dokument?






Poznámky redaktora
As steel girders may usually not drilled through, the only other option fastening with construction clamps.g. Construction clamp, type 5010, able carry lightning current TBS Blitzschutz-Leitfaden 2018 / en / 2020/01/10 14:42:40 14:42:40 (LLExport_02613) / 2020/01/10 14:42:54 14:42:54 108 Chapter The external lightning protection system .2. At first, fastening support systems steel girders seems barely possible.7 Fastening steel structures In industrial construction, steel constructions are fre- quently used for the building structures.2. However, the supporting steel elements the building are unprotected, other technical equipment, e. steel girders are used natural con- ductor, they are connected the earthing system, then construction clamps able carry light- ning current must used. Thus, unprotected steel does not possess fire resistance, meaning that special measures are necessary, such treatment with fire protection coatings lining with non-com- bustible plates. smoke extraction auto- matic extinguishing systems, can compensate for the bad properties the steel case fire limiting the critical temperatures. However, approx. 500 °C, steel loses half its res- istance, that, there fire, the building struc- tures are exposed high risk. Steel girders and supports can also found power stations