Lightning protection guide by OBO

| Kategorie: Katalog  |

Last revision 2020

Vydal: OBO BETTERMANN s. r. o. Autor: OBO BETTERMANN

Strana 67 z 288

Jak získat tento dokument?






Poznámky redaktora
summer, the length of the air-termination systems and down-conductors changes. Material Expansion piece spacing m Steel 15 Stainless steel 10 Copper 10 Aluminium 10 Table 2.2 Changes length due temperature At higher temperatures, e.g. S shape), because they are flexible lines.1.5.0 total area 2.1. TBS Blitzschutz-Leitfaden 2018 / en / 2020/01/10 14:42:40 14:42:40 (LLExport_02613) / 2020/01/10 14:42:54 14:42:54 67 Chapter The external lightning protection system .4: Expansion pieces compensate changes in length due temperature 2. These temperature-related changes length must taken into account during installation.5: Incorporation roof structures Smoke and heat extraction roof light domes must protected from direct lightning strikes. Roof structures Dimensions Metal 0.g.3 above roof level 1.4 have proved effective. Surge protection devices protect the electrical drives these devices from damage due inductive coupling.TBS Blitzschutz-Leitfaden 2018 / en / 2020/01/10 14:42:40 14:42:40 (LLExport_02613) / 2020/01/10 14:42:54 14:42:54 2.3 External lightning protection for roof struc- tures Roof structures must incorporated into the external lightning protection system according IEC 62305-3 if they exceed the dimensions stated Table 2. Ex- pansion pieces must allow flexible response to changes length, either through their shape (e.5 above the air-termination system Table 2.0 length the structure Non-metal 0. For practic- al purposes, the expansion piece spacings listed in Table 2