Poznámky redaktora
The specific range and type, well as, the actual number of ballasts per luminaire must taken into account. case metal halide lamps, the switch-on current increased ignition time shunting. The levels indicated the table refer simulta- neous switch-on the mains voltage peak with 230 V.182 The Lighting Handbook Fusing and rating circuits Tripping values line circuit-breakers For the operation luminaires, automatic circuit breakers with characteristics are recommended. Please note: the values given the table are intended reference values only and may deviate individual cases. case multipolar circuit breakers, the values specified the manu- facturer must reduced 20%. case connection circuit breakers with characteristics, transformers should not loaded above rating order to avoid false tripping. Tripping characteristics Tripping current B (quick-acting) C 3 5-fold rated current 5 10-fold rated current