The Lighting Handbook ZG

| Kategorie: Firemní tiskovina  | Tento dokument chci!

Vydal: ZG Lighting Czech Republic s.r.o

Strana 103 z 244







Poznámky redaktora
system current 250 from central interface supply (each electronic ballast takes maximum of current load) – Two-wire control line (potential-free, polarity-free, unshielded, terminal resis­tors) – Voltage drop between transmitter and recei­ver must not more than V – Application: general lighting (small number of lighting points, static light) . – DALI not building management bus system, but protocol for digital address­ ing technical lighting control gear. scenes per control unit can be programmed – Bidirectional: reports information such as faulty lamps, dimming levels etc. control units per control circuit – Max. – DALI standard defined several manufacturers luminaires and electronic ballasts: IEC 60929 allows the combination of devices various manufacturers. – Max. However, the standard defines only output devices (control gear), not input devices such sensors control units. DALI: Features – Usable data transmission rate: 1200 bit/s – Max.103 The Lighting Handbook DALI: General information – The term DALI stands for “Digital Addressable Lighting Interface”. Hence, input devices with DALI connection are addressed manufacturer-specific way! – IEC 62386 specifies requirements placed on control gear allocated specific types of device. groups per control gear can be assigned – Max